Parámetros
problema comun
DA 284
Mounting
thread M40 x 1.5 or M12 x 1.5 with nut
Torque
M40: 5Nm (max. 10Nm), M12: 0.5Nm (max. 1Nm)
Depth in enclosure
M40: approx. 16mm, M12: approx. 8mm
Sealing
sealing gasket NBR
Material
plastic, light grey
Filter
waterproof membrane
Dimensions
M40: Ø 60 x 37mm, M12: Ø 17 x 17.5mm
Fitting position
variable
Installation: Make cut-out Ø 40.5+0.5mm in enclosure wall for size M40 or Ø 12+0.2mm for size M12, and mount pressure compensation device with nut. Please make sure that the sealing gasket is put in place on the outer side panel of the enclosure. For optimal pressure compensation we recommend to use two devices on opposite sides towards the top of the enclosure.
Pressure differentials in enclosures with a high degree of protection are a result of internal and external temperature changes. In the case of negative pressure or partical vacuum, dust and humidity can enter the enclosure through the door seal. When the air inside the enclosure cools down, condensation may occur because the humidity cannot escape the enclosure. The easy-to-install pressure compensation device DA 284 provides compensation of pressure at a protection degree of IP66 (M12: IP68). Even with a slight overpressure, a waterproof membrane inside the plug allows the humidity to escape whilst blocking water and dirt from entering the enclosure.